Do you have any questions about our products? Our experts will be glad to assist you! Just give us a call +358 20 7789810
Zoom
CUBE67 I/O EXTENSION MODULE
Tuote voi erota kuvan tuotteesta

CUBE67 I/O EXTENSION MODULE

4 analog inputs (I)
Tuotenro.: 56731
Paino: 0.17 kg
  Saatavilla
 Tuotevertailu
Listahinta / kpl:

Voisit olla kiinnostunut myös näistä

Expansion module
AI4 - (E) 4× M12 (I)
Current
Connection cables are in the online shop under "Connection Technology". Housing fully potted.
Input
Conversion time (analog) approx. 2 ms (per channel)
Sensor supply US 24 V DC (EN 61131-2), max. 200 mA (M12 female), short-circuit and overload protected
Resolution (analog) 15 Bit
Accuracy max. ±0.5% (of range limit)
Internal communication
Current consumption max. 50 mA
LED display US: sensor supply and internal supply voltage (green: OK); UA: actuator supply (green: OK)
Connections
Fieldbus via internal system connection
Sensor-system/actuator supply via internal system connection (max. 2× 4 A)
I/O ports M12 (female) 5-pole, A-coded
General data
Protection IP67
Mounting method 2-hole screw mounting
Temperature range 0...+55 °C (storage temperature -20...+75 °C)
Dimensions H×W×D 150×30×34.5 mm
Diagnostic
Communication status via LED
Diagnostic via LED per module and channel
Diagnostic via BUS per module and channel
Monitoring - under voltage yes
Monitoring - no voltage yes
Short-circuit and overload yes
Actuator warning per channel via LED and BUS
Wire break upper/lower limit overload per channel via LED and BUS
Current input signals
Load approx. 300 Ω, differential input
Input range 0...20 mA, 4...20 mA
Kaupalliset tiedot
Alkuperämää DE
EAN 4048879288057
eClass 27242601
Pakkauskoko 1
Tullinumero 85389099
 
Tuotetietoja:
  • Lataus Datalehti
  • Lataus Approvals and certificates 56731_E201820-NRAQ7_ulc_z_a.pdf
  • Lataus Approvals and certificates 56731_990-04.16_ce_z_b.pdf
  • Lataus Approvals and certificates 56731_E201820-NRAQ_ul_z_a.pdf
  • Lataus China RoHS information EPUP-20_CHR_x_1.pdf
  • Lataus Drawing Files 56611_stp_x_a.zip
  • Lataus Drawing Files 56731_p8_2_50.zip
  • Lataus Installation Instructions 56600_ina_6_36.pdf
  • Lataus Manuals 56970_hdb_x_25.zip
  • Lataus Manuals 56971_hdb_x_34.zip
* plus alv., plus toimituskulut