You might also like
INPUT: 3× 360...440 V AC
OUTPUT: 22...28 V DC
Current: 10 A
OUTPUT: 22...28 V DC
Current: 10 A
General data
Standards | IEC 61010-2-201, EN 61204-3, EN 55022 B |
---|---|
Mounting method | DIN-rail mountable TH35 (EN 60715), additional plate for screw mounting Art.-No. 89500 |
Efficiency | 90% |
Relative humidity | 30...90%, no condensation |
Dimensions H×W×D | 132×198×97 mm |
Temperature range | 0...+60 °C (storage temperature -25...+85 °C) |
Output
Output voltage | 24 V DC (SELV), ±1%; 22...28 V adjustable |
---|---|
Output current | 10 A (+60 °C); 12 A (+40 °C) |
Mains failure bridging time | min. 3 ms (400 V AC) |
Ripple | max. 20 mV eff/rms |
Spikes | max. 100 mV ss/pp |
Unit protection | short-circuit and overload protected |
Phase monitoring | Switching off during 2-phase operation |
LED display | LED (green): in operation; LED (red): off; LED (yellow): pre-warning when overheated or overloaded |
Parallel usage/serial usage | yes/yes |
Input
Input voltage | 3× 360...440 V AC |
---|---|
Primary fusing external | max. 10 A |
Frequency | 50...60 Hz |
Input current | 3× 0.42 A |
Commercial data
country of origin | CZ |
---|---|
customs tariff number | 85044090 |
EAN | 4048879080637 |
eClass | 27049002 |
Packaging unit | 1 |